HOME   Industry Type Products    All Products
 


• About P-72
• Pipe Dimensions / Fittings
• P-72 Sheet & Weld Rod
• Piping Design Properties
• Installation of P-72
• P-72 Application Photos

Prince P-72 Styrene Copolymer
Solvent Cement & Primer

Part No.

Size

P72C-QT (cement)

Quart

P72P-QT (primer)

Quart




Estimated  Quantities of Prince P-72
Cement* for Socket Welding Per Quart

Size Fitting

No. of Joints

No. of Couplings

No. of Tees

1/2"

380

190

127

3/4"

240

120

80

1"

200

100

66

1-1/ 4"

140

70

48

1-1/ 2"

100

50

33

2"

60

30

20

2-1/ 2"

50

24

16

3"

40

20

12

4"

32

16

10

5"

24

12

8

6"

12

6

4

8"

6

3

2

10"

4

2

1

12"

2

1

2/3

* Estimated quantities of Prince P-72 cement can vary due to installation conditions, tolerance variations, and socket depth; consequently, this information should be used as a guide not a guarantee. 


Prince P-72 Cement Socket Ends System Maximum
Operating Pressure (PSI) at 73° F (21.0° C)
 Table III

Pipe Size

Schedule 40

Schedule 80

1/2 "

324

428

3/4 "

269

367

1"

253

340

1-1 /4"

191

263

1-1 /2"

162

229

2"

177

240

2-1 /2"

154

214

3"

132

187

4"

116

169

6"

106

163

8"

93

145

**10"

85

138

**12"

80

135

**14"

78

134

**16"

78

132

**18"

78

130


Most applications for chlor-alkali and chlorate are at low pressures. The data provided for Flanged End Systems and Temperature/Pressure Correction Factors must be fully adhered to. We suggest that higher pressure applications be discussed with our field personnel  before proceeding.

NOTES:
** 1. No standard pressure rated fittings available for these sizes. Check with us for availability of custom fittings.
2. Pressure ratings  of threaded pipe must be derated 50% from the above table (e.g. 1" Sch 80 threaded connections rated at 50% of 340 psi  = 170 psi at 73 deg.F)


P-72 Temperature Correction Factors
Table IV

°C

°F

Factor

21.0

70

1.0 0

26.8

80

.96

32.1

90

.92

38.0

100

.85

43.0

110

.77

46.1

115

.74

49.0

120

.70

51.7

125

.66

54.0

130

.62

60.0

140

.55

65.0

150

.47

71.0

160

.40

76.0

170

.32

83.0

180

.25

93.0

200

.18


To obtain pressures at elevated temperatures, please multiply the above correction factor at desired temperatures by the maximum operating pressure at 73° F as shown on Table III.

Flanged  End System Maximum Operating Pressure PSI
Table V

°C

°F

PSI

38.0

100

150

43.0

110

145

49.0

120

135

54.0

130

125

60.0

140

110

65.0

150

95

71.0

160

75

76.0

170

65

83.0

180

55

88.0

190

48

93.0

200

40

10" and larger sizes-check with factory for pressure rating.
Important
Maximum pressure for any flanged system is 150 psi unless otherwise  noted. At elevated temperatures the pressure capability of the  flanged system must be derated as noted above.

Support Spacings - Schedule 40 - P-72 Pipe

Temp: °F
Temp: °C

60
15.6

80
26.8

100
37.7

120
49.0

140
60.0

160
71.0

180
83.0

200
93.0

INCHES

Feet

Feet

Feet

Feet

Feet

Feet

Feet

Feet

1/4

4

3-3/4

3-1/2

3-1/4

2-3/4

2-1/2

2

1-1/2

1/2

4-1/2

4-1/4

4

3-3/4

3-1/4

3

2-1/2

2

3/4

5

4-3/4

4-1/2

4-1/4

3-3/4

3-1/4

2-3/4

2

1

5-1/2

5-1/4

4-3/4

4-1/2

4

3-1/2

3

2-1/4

1-1/4

6

5-1/2

5-1/4

4-3/4

4-1/4

3-3/4

3-1/4

2-1/4

1-1/2

6-1/2

6

5-1/2

5

4-1/2

4

3-1/2

2-1/2

2

7

6-1/2

6

5-1/2

5

4-1/4

3-3/4

2-3/4

2-1/2

7-1/2

7-1/4

6-3/4

6-1/4

5-1/2

4-3/4

4

3

3

7-3/4

7-1/2

7

6-1/2

6

5-1/4

4-1/4

3-1/4

4

8-1/4

8

7-1/2

7

6-1/4

5-1/2

4-3/4

3-1/2

6

8-3/4

8-1/2

8

7-1/2

6-3/4

6

5

4

8

9-1/4

9

8-1/2

8

7-1/4

6-1/2

5-1/2

4-1/4

10

9-3/4

9-1/2

9

8-1/2

7-3/4

7

6

4-1/2

12

10-1/4

10

9-1/2

9

8-1/4

7-1/2

6-1/2

4-3/4



Support  Spacings - Schedule 80 - P-72 Pipe

Temp: °F
Temp: °C

60
15.6

80
26.8

100
37.7

120
49.0

140
60.0

160
71.0

180
83.0

200
93.0

INCHES

Feet

Feet

Feet

Feet

Feet

Feet

Feet

Feet

1/4

4

4

3-3/4

3-1/2

3-1/4

2-3/4

2-1/2

2

1/2

5

4-3/4

4-1/2

4-1/4

3-3/4

3-1/4

3

2-1/4

3/4

5-1/2

5-1/4

5

4-3/4

4-1/4

3-1/2

3-1/4

2-1/2

1

6

5-3/4

5-1/2

5

4-1/2

4

3-1/2

2-3/4

1-1/4

6-1/2

6-1/4

5-3/4

5-1/4

4-3/4

4-1/4

3-3/4

2-3/4

1-1/2

6-3/4

6-1/2

6

5-1/2

5

4-1/2

4

3

2

7-1/2

7

6-1/2

6

5-1/2

4-3/4

4-1/4

3-1/4

2-1/2

8-1/4

7-3/4

7-1/2

7

6-1/4

5-1/2

4-1/2

3-1/2

3

9

8-1/2

8

7-1/2

6-3/4

5-3/4

5

4

4

9-3/4

9-1/4

8-3/4

8

7-1/4

6-1/4

5-1/4

4-1/4

6

10-1/4

9-3/4

9-1/4

8-1/2

7-3/4

6-3/4

5-3/4

4-1/2

8

10-3/4

10-1/4

9-3/4

9-1/4

8-1/2

7-1/2

6-1/2

5-1/4

10

11-1/4

10-3/4

10-1/4

9-1/2

8-3/4

7-3/4

6-3/4

6

12

11-3/4

11-1/4

10-3/4

10

9-1/4

8-1/4

7-1/4

6-1/2

The above data is based on fluids with a specific gravity of 1.0.
For heavier fluids, the support spacing from the charts should be multiplied by the following correction factor:


Sp. Gr.

Correction Factor

 

1.0

1.00

1.1

0.98

1.2

0.96

1.4

0.93

1.6

0.90

2.0

0.85

2.5

0.80

For support spacing at higher temperatures than listed, please consult us.

 
 

[ Home  |  About Prince  | Prince News | Contact Us / RFQ  |  Request Literature ]